Steel that passes through the building envelope acts as a thermal bridge: in winter its warm-side surface gets cold, and once it drops below the dew point, moisture condenses on bolt heads and plates and can lead to damp and mould. Use this free checker (beta) to find the dew point for your indoor conditions, the minimum temperature index a connection needs, and whether a detail passes.
For preliminary checks only. Dew point uses the Magnus formula. The temperature index is (surface temperature − outdoor temperature) ÷ (indoor temperature − outdoor temperature); a connection whose warm-side surface stays above the dew point will not form surface condensation at these conditions. The steel surface temperature should come from thermal modelling or measurement of the actual detail.
To raise the surface temperature at a steel connection, use an STB-1 Structural Thermal Break pad between the steel members and thermal washers and Thermal Bushings at the bolts.